The ATEX-approved 3G category of ESX10 and ESX10-T are intended for the use in Ex zone 2, making them particularly useful for applications in process control in the chemical, petroleum and gas industries.
The compact E-T-A ESX10 and ESX10-T Electronic Circuit Breakers are just 12.5mm wide and both provide electronic overcurrent protection for 24V DC (and 12V DC ESX10-T only) control circuits with load currents from 0.5A to 12A. In the event of overload or a short circuit, the faulty load will be disconnected electronically by means of a MOSFET in the output circuit of the protector. They provide the best possible protection for loads, such as controls, sensors, transformers and solenoid valves, which are fed by switch-mode power supplies or battery-buffered power supplies.
The E-T-A ESX10/ESX10-T provide active current limitation to 1.8 or 1.5 times its rated current. This allows capacitive loads of up to 20,000μF or lamp loads to be switched on without affecting other loads on the power supply. At the same time, this electronic active current limitation responds much faster to overload or short circuit conditions than switch-mode power supplies: it will shutdown electronically a single faulty output, while allowing all other load circuits connected to the same SMPS to continue working as normal.
Status indication is provided by a multicolour LED plus an integral short-circuit proof status output or potential-free signal contact. In the event of an overload or short circuit, the load circuit may be re-activated by a manual ON/OFF button, or, as an option, electronically via a re-set input. The ON/OFF button also allows manual disconnection when starting up a system or during maintenance.